AEPAmerican Electronic
Products. Inc.
GET A QUOTE
← HVAC PRODUCT FAMILIES
Electronic Pressure Sensors

Electronic Pressure Sensors

DYK pressure sensors use a ceramic piezoresistive element to convert pressure to a voltage or current signal for HVAC and refrigeration controls. The catalog lists up to 50 bar, −40 to 125 °C operating temperature, and IP67 shell protection.

REQUEST A QUOTE → View all specifications ↓

DYK Series Electronic Pressure Sensor

DYK sensors use a dry ceramic piezoresistive element and an amplifier IC to convert measured pressure into a standard voltage or current signal for automotive, HVAC and refrigeration controls.

  • Integrated signal conditioning, automated surface-mount assembly and laser trimming support accurate, consistent measurements, stable output and fast response.
  • Built-in circuit protection covers overvoltage, overcurrent and reverse polarity. The manufacturer reports EMC testing for resistance to electromagnetic interference.
  • The compact, standardized housing simplifies installation.
DYK Series Electronic Pressure Sensor
DYK sensor specifications
ParameterValue
Measurement range0–50 bar across the series
Voltage version supply5 VDC ±0.25 V
Voltage version protection16 V positive overvoltage, −14 V reverse voltage
Current version supply8–30 VDC, reverse-polarity protection
Voltage output0.5–4.5 V proportional to pressure
Current output4–20 mA
Combined accuracy±2.5% full scale
Operating temperature−40 to +125 °C
Response time<1 ms
Temperature shift±0.02% full scale/°C
Linearity, hysteresis and repeatabilityWithin ±0.5% full scale
StabilityBetter than 0.15% full scale per year
Shell materialCopper
Shell protectionIP67
Process connection7/16–20 UNF female flare, optional custom fitting
ConnectorPackard Metri-Pack
Voltage wiringRed power, black ground, green output
DYK sensor outline and connector pins
DYK sensor outline and connector pins

Pressure ranges and output curves

Each signal type covers five pressure ranges. The model table and curves use the same part numbers.

Pressure ranges and signal outputs
ModelPressure range (MPa)SignalSupply (VDC)
DYK BA010DV5-4.50–10.5–4.5 V5 ±0.25
DYK BA020DV5-4.50–20.5–4.5 V5 ±0.25
DYK BA034DV5-4.50–3.40.5–4.5 V5 ±0.25
DYK BA042DV5-4.50–4.20.5–4.5 V5 ±0.25
DYK BA050DV5-4.50–50.5–4.5 V5 ±0.25
0.5–4.5 V · DYK BA010DV5-4.5 · Voltage (V) vs. pressure (MPa)
0.5–4.5 V · DYK BA010DV5-4.5 · Voltage (V) vs. pressure (MPa)
0.5–4.5 V · DYK BA020DV5-4.5 · Voltage (V) vs. pressure (MPa)
0.5–4.5 V · DYK BA020DV5-4.5 · Voltage (V) vs. pressure (MPa)
0.5–4.5 V · DYK BA034DV5-4.5 · Voltage (V) vs. pressure (MPa)
0.5–4.5 V · DYK BA034DV5-4.5 · Voltage (V) vs. pressure (MPa)
0.5–4.5 V · DYK BA042DV5-4.5 · Voltage (V) vs. pressure (MPa)
0.5–4.5 V · DYK BA042DV5-4.5 · Voltage (V) vs. pressure (MPa)
0.5–4.5 V · DYK BA050DV5-4.5 · Voltage (V) vs. pressure (MPa)
0.5–4.5 V · DYK BA050DV5-4.5 · Voltage (V) vs. pressure (MPa)

Discuss your requirements

Share the pressure range, media, signal and supply, process fitting, and electrical connector.

CONTACT AEP →