HVAC / Motors
BLDC & EC Motors
MWS brushless motors cover fan coil, duct, and outdoor fan applications. Drive placement and shaft configuration vary by motor. The MWS EC range also includes mains-powered freezer fan motors.
REQUEST A QUOTE → View all specifications ↓MWS fan coil motors
Brushless motors for fan coil units, with internal or external drives depending on the configuration.
- The 8A-PD design uses a BMC-encapsulated stator and external sensorless drive. The integrated-drive 8K design uses customer-supplied DC power.
- Single and double shafts are available. Variable-speed versions support PWM control and can include a reverse-control input.
External sensorless drive. BMC-encapsulated stator and single or double shaft options.
| Model | Supply | Current (A) | Input (W) | Output (W) | Speed (rpm) | Efficiency (%) | Ingress protection |
|---|---|---|---|---|---|---|---|
| MWS20-8A-PD | 280-380VDC | 0.10/0.07 | 27 | 20 | 1500 | 75 | IP44 |
| MWS30-8A-PD | 280-380VDC | 0.14/0.11 | 40 | 30 | 1500 | 75 | IP44 |
| MWS50-8A-PD | 280-380VDC | 0.24/0.18 | 67 | 50 | 1500 | 75 | IP44 |
| Parameter | Value |
|---|---|
| Ambient temperature | −20 to +50 °C |
| Storage temperature | −30 to +60 °C |
| Output range | 20–50 W |
| Insulation class | B |
| Bearing and mounting | Ball bearing, horizontal mounting |
| Direction of rotation | Specified to order |
| Drive | Sensorless, 180° sine-wave SVPWM |
| Protection functions | Phase current, short circuit and overtemperature |
Integrated drive with customer-supplied DC power. Single or double shaft options.
| Model | Supply | Current (A) | Input (W) | Output (W) | Speed (rpm) | Efficiency (%) | Ingress protection |
|---|---|---|---|---|---|---|---|
| MWS30-8K | 280-380 VDC | 0.14/0.10 | 40 | 30 | 1350 | 75 | IP42 |
| MWS50-8K | 280-380 VDC | 0.23/0.17 | 67 | 50 | 1350 | 75 | IP42 |
| MWS70-8K | 280-380 VDC | 0.32/0.25 | 93 | 70 | 1350 | 75 | IP42 |
| MWS90-8K | 280-380 VDC | 0.42/0.32 | 120 | 90 | 1350 | 75 | IP42 |
| MWS110-8K | 280-380 VDC | 0.52/0.38 | 146 | 110 | 1350 | 75 | IP42 |
| MWS125-8K | 280-380 VDC | 0.6/0.44 | 166 | 125 | 1350 | 75 | IP42 |
| Parameter | Value |
|---|---|
| Ambient temperature | −15 to +50 °C |
| Storage temperature | −30 to +60 °C |
| Output range | 30–125 W |
| Insulation class | B |
| Bearing and mounting | Ball bearing, horizontal mounting |
| Direction of rotation | Specified to order |
| Drive | Sensorless, 180° sine-wave SVPWM |
| Protection functions | Phase current, short circuit and overtemperature |
Fan-coil motors use sensorless PWM speed control. The controller can be supplied with a reverse-control input.
| Model | Power (W) | Supply | Speed range (rpm) | Ingress protection | Efficiency |
|---|---|---|---|---|---|
| MWS30-8K | 30 | DC380V, DC310, DC280 | 300-1500 | IP20 | 74% |
| MWS60-8K | 60 | DC380V, DC310, DC280 | 300-1500 | IP20 | 75% |
| MWS80-8K | 80 | DC380V, DC310, DC280 | 300-1500 | IP20 | 75% |
| MWS60-8E-S | 60 | AC200V, AC240V, AC260V | 300-1500 | IP44 | 78% |
| MWS120-8E-S | 120 | AC200V, AC240V, AC260V | 300-1500 | IP44 | 78% |
MWS outdoor fan motors
Outdoor fan motors with drive and enclosure options that vary by model.
- The 10K-PD uses a ten-pole rotor and an integrated drive supplied with 540 VDC.
- The larger 8A-PD configuration uses an external drive, a shaft seal and a sealed cable entry.
Outdoor fan motor with a single shaft and integrated drive.
| Model | Supply | Current (A) | Input (W) | Output (W) | Speed (rpm) | Efficiency (%) | Ingress protection |
|---|---|---|---|---|---|---|---|
| MWS80-8K-PD | 280-380VDC | 0.37/0.27 | 103 | 80 | 900 | 78 | IP44 |
| MWS100-8K-PD | 280-380VDC | 0.46/0.34 | 128 | 100 | 900 | 78 | IP44 |
| MWS130-8K-PD | 280-380VDC | 0.62/0.46 | 173 | 130 | 900 | 75 | IP44 |
| Parameter | Value |
|---|---|
| Ambient temperature | −20 to +50 °C |
| Storage temperature | −30 to +60 °C |
| Output range | 80–130 W |
| Insulation class | B |
| Bearing and mounting | Ball bearing, horizontal mounting |
| Direction of rotation | Specified to order |
| Drive | Sensorless, 180° sine-wave SVPWM |
| Protection functions | Phase current, short circuit and overtemperature |
Outdoor fan motor with a choice of internal or external drive and copper or aluminum windings.
| Model | Supply | Current (A) | Input (W) | Output (W) | Speed (rpm) | Efficiency (%) | Ingress protection |
|---|---|---|---|---|---|---|---|
| MWS100-8K | 280-380 VDC | 0.48/0.35 | 134 | 100 | 800 | 75 | IP44 |
| MWS130-8K | 280-380 VDC | 0.62/0.46 | 173 | 130 | 800 | 75 | IP44 |
| MWS150-8K | 280-380 VDC | 0.71/0.53 | 200 | 150 | 820 | 75 | IP44 |
| MWS170-8K | 280-380 VDC | 0.81/0.6 | 226 | 170 | 820 | 75 | IP44 |
| MWS190-8K | 280-380 VDC | 0.9/0.67 | 253 | 190 | 820 | 75 | IP44 |
| Parameter | Value |
|---|---|
| Ambient temperature | −15 to +50 °C |
| Storage temperature | −30 to +60 °C |
| Output range | 100–190 W |
| Insulation class | B |
| Bearing and mounting | Ball bearing, horizontal mounting |
| Direction of rotation | Specified to order |
| Drive | Sensorless, 180° sine-wave SVPWM |
| Protection functions | Phase current, short circuit and overtemperature |
The catalog lists IP44 in the model table and IP42 in the general operating notes. Confirm the required rating for the selected configuration.
| Model | Supply | Current (A) | Input (W) | Output (W) | Speed (rpm) | Efficiency (%) | Ingress protection |
|---|---|---|---|---|---|---|---|
| MWS450-8A-PD | 280-380 VDC | 2/1.5 | 562 | 450 | 1150 | 80 | IP44 |
| MWS550-8A-PD | 280-380 VDC | 2.5/1.8 | 687 | 550 | 1100 | 80 | IP44 |
| MWS750-8A-PD | 280-380 VDC | 3.4/2.5 | 937 | 750 | 1050 | 80 | IP44 |
| MWS920-8A-PD | 280-380 VDC | 4.1/3.1 | 1150 | 920 | 950 | 80 | IP44 |
| Parameter | Value |
|---|---|
| Ambient temperature | −15 to +50 °C |
| Storage temperature | −30 to +60 °C |
| Output range | 450–920 W |
| Insulation class | B |
| Bearing and mounting | Ball bearing, horizontal mounting |
| Direction of rotation | Specified to order |
Integrated drive, customer-supplied 540 VDC and a ten-pole rotor.
| Model | Supply | Current (A) | Input (W) | Output (W) | Speed (rpm) | Efficiency (%) | Ingress protection |
|---|---|---|---|---|---|---|---|
| MWS700-10K-PD | 540VDC | 1.51 | 814 | 700 | 1180 | 86 | IP44 |
| MWS900-10K-PD | 540VDC | 1.94 | 1047 | 900 | 1180 | 86 | IP44 |
| MWS1100-10K-PD | 540VDC | 2.40 | 1294 | 1100 | 1180 | 85 | IP44 |
| MWS1350-10K-PD | 540VDC | 2.98 | 1607 | 1350 | 1180 | 84 | IP44 |
| Parameter | Value |
|---|---|
| Ambient temperature | −20 to +50 °C |
| Storage temperature | −30 to +60 °C |
| Output range | 700–1,350 W |
| Insulation class | B |
| Bearing and mounting | Ball bearing, horizontal mounting |
| Direction of rotation | Specified to order |
| Drive | Sensorless, 180° sine-wave SVPWM |
| Protection functions | Phase current, short circuit and overtemperature |
Internal and external drives are available. Internal-drive versions use an aluminum enclosure.
| Model | Power (W) | Supply | Speed range (rpm) | Ingress protection | Efficiency |
|---|---|---|---|---|---|
| MWS180-8K | 180 | DC250V | 300-1300 | IP54 | ≥79% |
| MWS250-8K | 250 | DC250V | 300-1300 | IP54 | ≥80% |
| MWS380-8K | 380 | DC339V | 300-1300 | IP54 | ≥81% |
| MWS450-8K | 450 | DC339V | 300-1300 | IP54 | ≥82% |
| MWS500-8K | 500 | DC380V | 300-1300 | IP54 | ≥83% |
| MWS50-8K | 50 | DC24V | 300-1300 | IPX4 | ≥75% |
| MWS150-8K | 150 | DC48V | 300-1300 | IPX4 | ≥75% |
External sensorless drive with a neodymium rotor, shaft seal and sealed cable entry.
| Model | Supply | Current (A) | Input (W) | Output (W) | Speed (rpm) | Efficiency (%) | Ingress protection |
|---|---|---|---|---|---|---|---|
| MWS1500-8A-PD | 310-540VDC | 5.44/3.12 | 1685 | 1500 | 950 | 89 | IP44 |
| MWS1800-8A-PD | 310-540VDC | 6.60/3.79 | 2045 | 1800 | 950 | 88 | IP44 |
| MWS2100-8A-PD | 310-540VDC | 7.70/4.42 | 2386 | 2100 | 950 | 88 | IP44 |
| Parameter | Value |
|---|---|
| Ambient temperature | −30 to +50 °C |
| Storage temperature | −35 to +60 °C |
| Output range | 1,500–2,100 W |
| Insulation class | B |
| Bearing and mounting | Ball bearing, horizontal mounting |
| Direction of rotation | Specified to order |
| Drive | Sensorless, 180° sine-wave SVPWM |
| Protection functions | Phase current, short circuit and overtemperature |
MWS indoor duct fan motors
External-drive motors for indoor duct units. The power supply is available to order.
Indoor duct motor with an external drive and power supply available to order.
| Model | Power (W) | Supply | Speed range (rpm) | Ingress protection | Efficiency | Shaft |
|---|---|---|---|---|---|---|
| MWS230-8D/S | 230 | 310 / 380 VDC | 300–1,500 | IP20–IP44 | 80% | Single or double |
| MWS600-8D/S | 600 | 310 / 380 VDC | 300–1,500 | IP20–IP44 | 85% | Single or double |
| MWS900-8D/S | 900 | 310 / 380 VDC | 300–1,500 | IP20–IP44 | 85% | Single or double |
| MWS1250-8D/S | 1250 | 310 / 380 VDC | 300–1,500 | IP20–IP44 | 85% | Single or double |
MWS EC freezer motors
Mains-powered EC motors for freezer fans and similar refrigeration equipment.
| Model | Voltage (VAC) | Frequency (Hz) | Current (A) | Input (W) | Output (W) | Speed (rpm) |
|---|---|---|---|---|---|---|
| MWS7-4E-D | 220-240 | 50/60 | 0.12 | 14 | 7 | 1300 |
| MWS7-4E-S | 115 | 50/60 | 0.13 | 11 | 7 | 1550 |
| MWS10-4E-D | 220-240 | 50/60 | 0.14 | 17 | 10 | 1300 |
| MWS10-4E-S | 115 | 50/60 | 0.21 | 16 | 10 | 1550 |
| MWS16-4E-D | 220-240 | 50/60 | 0.25 | 30 | 16 | 1300 |
| MWS16-4E-S | 115 | 50/60 | 0.40 | 25 | 16 | 1550 |
| MWS20-4E-D | 220-240 | 50/60 | 0.25 | 30 | 20 | 1500 |
| MWS25-4E-D | 220-240 | 50/60 | 0.30 | 36 | 25 | 2300 |
| Parameter | Value |
|---|---|
| Ambient temperature | −30 to +50 °C |
| Ingress protection | IP54 |
| Insulation class | B |
| Rotation | CCW |
| Bearing and mounting | Ball bearing, any mounting orientation |
External-rotor BLDC motors
Compact external-rotor motors for fresh-air systems and thin fan assemblies.
- The Hall-less design places the power supply and drive at the motor end.
- The drive supports 0–10 VDC analog or PWM speed control, with serial control available for centralized systems.
The catalog prints the current for the 3,100 rpm MWS100-8E-D as “14./1.1”. Confirm the current for this configuration with AEP.
| Model | Supply | Frequency (Hz) | Current (A) | Input (W) | Output (W) | Speed (rpm) | Efficiency (%) | Ingress protection |
|---|---|---|---|---|---|---|---|---|
| MWS30-8E-D | 190-240VAC | 50/60 | 0.42/0.33 | 40 | 30 | 2000 | 75 | IP44 / IP20 |
| MWS50-8E-D | 190-240VAC | 50/60 | 0.7/0.56 | 67 | 50 | 2500 | 75 | IP44 / IP20 |
| MWS70-8E-D | 190-240VAC | 50/60 | 0.98/0.77 | 93 | 70 | 2800 | 75 | IP44 / IP20 |
| MWS90-8E-D | 190-240VAC | 50/60 | 1.26/1 | 120 | 90 | 3000 | 75 | IP44 / IP20 |
| MWS100-8E-D | 190-240VAC | 50/60 | 14./1.1 | 135 | 100 | 3100 | 75 | IP44 / IP20 |
| Parameter | Value |
|---|---|
| Ambient temperature | −25 to +60 °C |
| Storage temperature | −30 to +70 °C |
| Output range | 30–100 W |
| Insulation class | B |
| Rotation | Specified to order |
| Bearing and mounting | Ball bearing, horizontal or vertical |
| Drive | Sensorless, 180° sine wave |
| Speed control | 0–10 VDC analog, PWM or optional serial control |
| Protection | Phase current, short circuit and overtemperature |
| Model | Supply | Frequency (Hz) | Current (A) | Input (W) | Output (W) | Speed (rpm) | Efficiency (%) | Ingress protection |
|---|---|---|---|---|---|---|---|---|
| MWS100-8E-D | 190-240VAC | 50/60 | 0.7/0.55 | 130 | 100 | 1800 | 77 | IP44 / IP20 |
| MWS120-8E-D | 190-240VAC | 50/60 | 0.83/0.66 | 156 | 120 | 2200 | 77 | IP44 / IP20 |
| MWS140-8E-D | 190-240VAC | 50/60 | 0.98/0.77 | 182 | 140 | 2500 | 77 | IP44 / IP20 |
| MWS160-8E-D | 190-240VAC | 50/60 | 1.1/0.88 | 207 | 160 | 2660 | 77 | IP44 / IP20 |
| MWS180-8E-D | 190-240VAC | 50/60 | 1.25/1.0 | 233 | 180 | 2850 | 77 | IP44 / IP20 |
| Parameter | Value |
|---|---|
| Ambient temperature | −25 to +60 °C |
| Storage temperature | −30 to +70 °C |
| Output range | 100–180 W |
| Insulation class | B |
| Rotation | Specified to order |
| Bearing and mounting | Ball bearing, horizontal or vertical |
| Drive | Sensorless, 180° sine wave |
| Speed control | 0–10 VDC analog, PWM or optional serial control |
| Protection | Phase current, short circuit and overtemperature |
OEM PROJECTS
Discuss your requirements
Share the supply voltage, required output and speed, drive location, shaft dimensions, and mounting interface.
American Electronic